DT 4/24

DT is a complex range of surge protection devices designed for protection of data, communication, measuring and control lines against surge effects. These surge protection devices are recommended for use in the Lightning Protection Zones Concept at the boundaries of LPZ 0A(B) -1 according to EN 62305. All types provide effective protection of connected equipment against common mode and differential mode surge effects according to IEC 61643-21. The rated load current of individual protected lines IL < 0,1A.

These devices consist of gas discharge tubes, series impedance and transils. The number of protected pairs is optional (1-4). These devices are produced for nominal voltage within the range of 6V-170V. Maximum discharge current is 10kA (8/20), in case of “L” design the maximum discharge current is 20kA (8/20). For the protection of telephone lines it is recommended to use DT type with nominal voltage UN=170V (with code mark “T”).

Dimension drawing
Dimension drawing
PARAMETERS
Number of protected pairs 4
Nominal voltage UN 24 V
Maximum continuous operating voltage UC 28,6 V
Rated load current IL 100 mA
C2 Max. discharge current (8/20) Imax 10 kA
C2 Nominal discharge current ln (8/20) In 1 kA
C2 Voltage protection level at In UP 64 V
C3 Voltage protection level at 1 kV/µS UP 34 V
Response time tA < 30 ns
Data rate 1 MBit/s
Series impedance per line R 1,5 -10 Ω
Parasitic capacitance C 1,5 nF
Recommended section of the connected conductors S 0,25 - 1,5 mm2
Category tested acc. to IEC 61643:21-2000 A2, B2, C2, C3, D1
Article number 48 403
DOWNLOADS
Catalogue
EC declaration of conformity (82.4 KB) for registered only