DTNVE 0,5 is a complex range of surge protection devices designed for protection of data, communication, measuring and control lines against surge effects. These surge protection devices are recommended for use in the Lightning Protection Zones Concept at the boundaries of LPZ 0A(B) – 1 according to EN 62305. All types provide effective protection of connected equipment against common mode and differential mode surge effects according to IEC 61643-21. The rated load current of individual protected lines IL < 0,5A. These devices consist of gas discharge tubes, series impedance and transils. The number of protected pairs is optional (1-2). These devices are produced for nominal voltage within the range of 6V-115V. Maximum discharge current is 10kA (8/20).

Dimension drawing
Dimension drawing
PARAMETERS
Number of protected pairs 2
Nominal voltage UN 48 V
Maximum continuous operating voltage UC 57,6 V
Rated load current IL 0,5 A
D1 Lightning impulse current (10/350) Iimp 5 kA
Possibility changes of working parameters 2,5 kA
C2 Max. discharge current (8/20) Imax 10 kA
C2 Nominal discharge current ln (8/20) In 1 kA
C2 Voltage protection level at In UP 85 V
C3 Voltage protection level at 1 kV/µS UP 66 V
Response time tA < 30 ns
Series impedance per line R 4,7 µH
Parasitic capacitance C 1,5 nF
Recommended section of the connected conductors S 0,25 - 1.5 mm2
Category tested acc. to IEC 61643:21-2000 C1, C2, C3, D1
Article number 42 311