H40-L/12

H40-L/12 is designed for coaxial lines protection of 50Ω or 75Ω against induced surge effects in the Lightning Protection Zones Concept at the boundaries of LPZ 0A(B) – 1 according to EN 62305. These devices are especially used for protection of cameras and video signal concentrators. They are applicable to security and fire systems. H40-L version is equipped with more efficient nonlinear elements to reach higher discharge current up to 6,5kA (8/20). 

Dimension drawing
Dimension drawing
PARAMETERS
Number of protected pairs 4
Connector type BNC (F/F, F/M)
Nominal voltage UN 12 V
Maximum continuous operating voltage UC 14,4 V
Rated load current IL 300 mA
C2 Max. discharge current (8/20) Imax 6,5 kA
C2 Nominal discharge current ln (8/20) In 1 kA
C2 Voltage protection level at In UP 44 V
C3 Voltage protection level at 1 kV/µS UP 20 V
Response time tA < 30 ns
Parasitic capacitance C < 47 pF
Series impedance per line R 10 Ω
Category tested acc. to IEC 61643:21-2000 A2, B2, C2, C3, D1
Article number 52 413
CERTIFICATIONS
DOWNLOADS
Catalogue