HDT/6/24-F* is a range of combined two-stage surge protection intended for a low voltage data and power supply lines routed by a common cable. An example might be a pair of RS485 data line wires and a pair of 24 V DC power line wires routed by a common cable from the control system to remote sensors requiring an external supply voltage. The module can also be used to connect many other types of analog or digital sensors with symmetrical or asymmetrical output. The protection module must be installed just before the protected device. The 1st stage of surge protection consists of three-pole gas discharge tubes, the 2nd stage is using transils. The overcurrent protection of the power supply line is ensured by a PPTC resettable fuse. The fuse heats up during the overcurrent and its internal resistance increases by several levels. This will limit (not interrupt) the flowing current. The green LED has only an orientation function about the presence of voltage on the power supply line. To reset the resettable fuse, the circuit must be switched off and let the fuse cool down. Unlike a standard fuse, resettable fuses do not have to be changed, which can reduce the service interventions or make the service faster.
Ochrana datové linky | ||
Nominal voltage | Un | 6 V DC |
Maximum continuous operating voltage | Uc | 7,2 V DC |
Rated current | IL | 100 mA |
Power supply system protection | ||
Nominal voltage | UN | 24 V DC |
Maximum continuous operating voltage | UC | 28,6 V DC |
Rated current | IL | 1100 mA |
Hold-current of the resettable fuse at -40; 23; 70 °C | Ihold | 1790; 1100; 580 mA |
Trip-current of the resettable fuse at -40; 23; 70 °C | Itrip | 3580; 2200; 1160 mA |
C1 Nominal discharge current (8/20 µs) | In | 1 kA |
C1 Voltage protection level line-G at In line/G | Up | 40 V |
C2 Voltage protection level at In line/line | Up | 35 V |
C2 Nominal discharge current (8/20 µs) | In | 10 kA |
C2 Voltage protection level line-G at In line/G | Up | 60 V |
C2 Voltage protection level at In line/line | UP | 40 V |
C3 Voltage protection level line-G at 1 kV/µs | Up | 35 V |
C3 Voltage protection level at 1 kV/µS line/line | UP | 35 V |
Operating temperature | ϑ | -40 °C ÷ +70 °C |
Recommended section of the connected conductors | S | 0,25 ÷ 1,5 mm2 |
Degree of protection of enclosure | IP20 | |
Examinations according to | EN 61643-21 (IEC 61643-21:2000) | |
Article number | 56 101 |
Note: The current of the resettable fuse Ihold is a value valid for an ambient temperature of 23 °C at which the fuse has not tripped yet. The current Itrip is a value at which the fuse will definitely trip and this value is equal to twice the current Ihold. For another ambient temperature, the Ihold value must be multiplied by a coefficient according to the formula k=(123-Ta)/100 [-, °C], where Ta is the actual ambient temperature of the fuse.
Catalogue | |
2D model (618.35 KB) | for registered only |
3D model (324.38 KB) | for registered only |