HLSA12,5-275/3+1 M S (Hakel Ligtning Surge Arrester) of the „G-Line“ range is a lightning and surge arrester according to EN 61643-11:2012 (IEC 61643-11:2011) consisting of high energy varistors in combination with gas discharge tube, which ensures zero leakage current in the PE conductor. Its parameters enable usage in buildings with considerable levels of protection LPL III and LPL IV, such as small administration complexes, residential buildings, family houses or properties and halls without the incidence of persons and indoor equipment. The device is to be installed on the interface of LPZ 0 – LPZ 1 and higher zones according to standard EN 62305:2011 (IEC 62305:2010), closest to where overhead line enters the building i.e. in the main distribution boards.

Internal wiring diagram
Internal wiring diagram
Dimension drawing
Dimension drawing
Installation diagram
Installation diagram
PARAMETERS
Test class according to EN 61643-11:2012 (IEC 61643-11) TYPE 1+2, CLASS I+II
Network type TN-S, TT
Maximum continuous operating voltage UC 275 V AC / 350 V DC
Maximum discharge current Imax 50 kA
Impulse discharge current for class I test (10/350) L/N limp 12,5 kA
Charge L/N Q 6,25 As
Specific energy for class I test L/N W/R 39 kJ/Ω
Impulse discharge current for class I test (10/350) N/PE Iimp 50 kA
Charge N/PE Q 25 As
Specific energy for class I test N/PE W/R 625 kJ/Ω
Total discharge current (10/350) L1+L2+L3+N->PE Itotal 50 kA
Total discharge current (8/20) L1+L2+L3+N->PE Itotal 100 kA
Nominal discharge current for class II test (8/20) L/N In 25 kA
Nominal discharge current for class II test (8/20) N/PE In 50 kA
Voltage protection level Up < 1,25 kV
Temporary overvoltage (TOV) L/N UT 337 V/5 s
Temporary overvoltage (TOV) N/PE UT 1200 V/0,2 s
Response time L/N tA < 25 ns
Response time N/PE tA < 100 ns
Max. back-up fuse 160 A gL/gG
Short-circuit current rating at max. back-up fuse ISCCR 60 kArms
LPZ 0-1
Housing material Polyamid PA6, UL 94 V-0
Degree of protection of enclosure IP20
Operating temperature ϑ -40 °C ... +70 °C
Cross-section of the connected conductors (at tightening moment of clamps 3 Nm) 25 mm2 (solid)
16 mm2 (wire)
Method of assembly DIN rail 35 mm / any
Failure signalisation (S) optical function signalization target clear – ok / optical function signalization target red - fault
Potential free signal contact (S) (recommended cross-section of remote monitoring max.1 mm2) AC: 250 V / 1,5 A, DC: 250 V / 0,1 A
Lifetime min. 100 000 h
Weight m 543 g
Article number 16 094
NOTES

S indication specifies a version with remote monitoring.

M indication specifies a type of construction with removable module.

CERTIFICATIONS
DOWNLOADS
Catalogue
Installation instructions (1.54 MB)
2D model (691.19 KB) for registered only
3D model (1.46 MB) for registered only