HLSA25G-255/4+0

HLSA25G-255/4+0 (Hakel Ligtning Surge Arrester) of the „G-Line“ range is a lightning and surge arrester according to EN 61643-11:2012 (IEC 61643-11:2011). It consists of high energy double varistors for better discharge ability and a gas discharge tube connected in series, which ensures zero leakage current through the conductor. Its parameters enable usage in buildings with considerable levels of protection LPL I and LPL II, such as hospitals, banks, industrial and administration complexes, schools, shopping and sports centres or supermarkets. The device is to be installed on the interface of LPZ 0 – LPZ 1 and higher zones according to standard EN 62305:2011 (IEC 62305:2010), closest to where overhead line enters the building i.e. in the main distribution boards. The product has two PE terminals, which can not be used as a PE bridge.

Internal wiring diagram
Internal wiring diagram
Dimension drawing
Dimension drawing
Installation diagram
Installation diagram
PARAMETERS
Test class according to EN 61643-11:2012 (IEC 61643-11) TYP 1+2, CLASS I+II
Network type TN-S, TT
Maximum continuous operating voltage UC 255 V AC
Impulse discharge current for class I test (10/350) Iimp 25 kA
Charge Q 12,5 As
Specific energy for class I test W/R 156 kJ/Ω
Total discharge current (10/350) L1+L2+L3+N->PE Itotal 100 kA
Nominal discharge current for class II test (8/20) In 25 kA
Maximum discharge current Imax 50 kA
Total discharge current (8/20) L1+L2+L3+N->PE Itotal 200 kA
Voltage protection level at In Up < 1,2 kV
Temporary overvoltage (TOV) UT 337 V/5 s
Response time tA < 25 ns
Max. back-up fuse 250 A gL/gG
Max. back-up fuse („V“ connection) 125 A gL/gG
Short-circuit current capability 250 A gL/gG ISCCR 80 kArms
LPZ 0-1 and higher
Housing material Polyamid PA6, UL94 V-0
Degree of protection of enclosure IP20
Operating temperature ϑ -40 °C ... +70 °C
Cross-section of the connected conductors (at tightening moment of clamps 3 Nm) 35 mm2 (solid)
25 mm2 (wire)
Method of assembly DIN rail 35 mm / any
Failure signalisation (S) optical function signalization target clear – ok / optical function signalization target red - fault
Lifetime min. 100 000 h
Weight m 1024 g
Article number 10 465
CERTIFICATIONS
DOWNLOADS
Catalogue
Installation instructions (364.68 KB)
2D model (689.16 KB) for registered only