HSA-275 M S

HSA-275 M S (Hakel Surge Arrester) of the „G-Line“ range  is a surge arrester according to EN 61643-11:2012 (IEC 61643-11:2011) consisting of high energy varistors. Its parameters enable its use in complex circumstances. The device is to be installed on the interface of LPZ 1 – LPZ 2 and higher zones according to standard EN 62305:2011 (IEC 62305:2010), i.e. into subsidiary switchboards and control boxes.

 

Dimension drawing
Dimension drawing
Internal wiring diagram
Internal wiring diagram
Installation diagram
Installation diagram
PARAMETERS
Test class according to EN 61643-11:2012 (IEC 61643-11) TYPE 2+3, CLASS II+III
Maximum continuous operating voltage UC 275 V AC / 350 V DC
Maximum discharge current Imax 50 kA
Nominal discharge current for class II test (8/20) In 20 kA
Open circuit voltage Uoc 6 kV
Voltage protection level Up < 1,25 kV
Voltage protection level at UOC Up < 850 V
Temporary overvoltage (TOV) UT 337 V/5 s
Response time tA < 25 ns
Max. back-up fuse 160 A gL/gG
Short-circuit withstand capability 160 A gL/gG ISCCR 60 kArms
LPZ 1-3
Housing material Polyamid PA6, UL94 V-0
Degree of protection of enclosure IP20
Operating temperature ϑ -40 °C ... +70 °C
Cross-section of the connected conductors (at tightening moment of clamps 3 Nm) 25 mm2 (solid)
16 mm2 (wire)
Method of assembly DIN rail 35 mm / any
Failure signalisation (S) optical function signalization target clear – ok / optical function signalization target red - fault
Potential free signal contact (S) (recommended cross-section of remote monitoring max.1 mm2) AC: 250 V / 1,5 A, DC: 250 V / 0,1 A
Lifetime min. 100 000 h
Weight m 105 g
Article number 27 090
NOTES

S indication specifies a version with remote monitoring.

M indication specifies a type of construction with removable module.

CERTIFICATIONS
DOWNLOADS
Catalogue
Installation instructions (342.73 KB)
2D model (514.84 KB) for registered only
3D model (752.42 KB) for registered only